Freezer Floor Systems Frost heave prevention for freezer and cold storage floors
(901) 452-4516 A division of Thermal Equipment Sales Co., Inc. AboutContactRep Tools

Sheet 04 · Controls

Controls and monitoring

A frost heave system can fail quietly. The ground cools slowly, and by the time the floor moves the soil may be frozen deep. The controls have to find a failed circuit in hours, not after a season.

01What the controls must catch

Older heat cable controls watched current draw. That works for constant-wattage cable, where a healthy circuit draws a known current. Self-regulating cable draws different current as its temperature changes, so current alone cannot tell a healthy circuit from a damaged one.

Our panels confirm operation directly at the far end of each run and back it up with ground temperature:

  • Far-end voltage, per circuit. Voltage present at the far end when the PLC calls for heat confirms the solid-state relay, breaker and cable are all passing power. Voltage present when the PLC is not calling for heat means a relay has failed shorted.
  • End-of-run relay, per loop. A small relay at the end of each cable run proves continuity of that individual run.
  • Ground-fault and breaker status, per circuit. Auxiliary contacts on each breaker report a trip.
  • Ground temperature, per zone. An independent check that does not rely on any electrical reading, with a low-temperature alarm and a thermocouple break alarm.
Touchscreen titled Freezer Floor Control / Alarm showing set floor temperature and eight zone temperatures with heat on or off status
Fig. 1Operator screen: set floor temperature, zone temperatures and heat status for eight zones.

02System architecture

Control and monitoring block diagramIncoming power passes through a lockable main disconnect, then a branch breaker and ground-fault breaker for each circuit, then a solid-state relay to the heat cable loops in the floor. Far-end voltage, end-of-run relays, breaker status and thermocouples report back to the PLC, which drives the touchscreen, horn, beacon, remote alarm contacts and accepts a peak setback input.CONTROL PANELFREEZER FLOORBUILDINGIncoming power208–480 VBMS / alarm systemdry contact / 24 VDCUtility peak signalremote inputEthernet / ModbusoptionalMain disconnectlockable (LOTO)Breakerper circuitGFEP 30 mAper circuitSSRper circuitPLC + thermocouple inputssetpoint · alarms · fault log · timersFar-endvoltage senseColor touchscreenstatus · historyHorn + red beaconsilence push buttonControl transformer / 24 V supplyfusedHeat cable loopsself-regulating, in conduitEnd-of-run relaysone per loopThermocouplesType J, per zone— power - - - monitoring signal red = heating circuit
Fig. 2Control and monitoring block diagram. Each heating circuit has its own breaker, 30 mA ground-fault protection, solid-state relay and far-end voltage feedback.

03Monitored points

PointDetectsOperator sees
Ground temperatureZone below setpoint or below the low alarm limitZone temperature, heat on/off, low-temperature alarm and total time spent in alarm
Thermocouple circuitOpen or broken sensor leadSensor fault alarm with zone
Far-end voltageRelay failed open, breaker off, cable open; relay failed shortedCircuit fault with circuit number
End-of-run relayLoss of continuity on an individual runRun fault with location
Ground-fault breakerGround-fault or overcurrent tripBreaker fault with circuit number
Fault historyEvery event, with count per conditionLog with location, time in fault, troubleshooting steps and replacement part numbers

04Alarms and remote monitoring

05Temperature control

A PLC with thermocouple inputs holds each zone at a user-set temperature, which cannot be set below 32 °F. Each circuit is switched by a solid-state relay rated for heat cable inrush. Self-regulating cable already reduces its own output as the base warms; the controller switches it off entirely when the zone is at setpoint, which saves energy and reduces cable temperature cycling.

Peak setback. A remote 24 VDC input lowers the setpoint during utility peak-demand periods. The ground has enough thermal mass that a few hours of reduced heat do not affect it.

06Electrical protection

Main disconnectDoor-interlocked, lockable for lockout/tagout
Branch protectionDedicated breaker for each circuit, C-curve or otherwise rated for self-regulating cable inrush
Ground-fault protection30 mA ground-fault equipment protection on every heating circuit, with auxiliary contact to the PLC
Control powerControl transformer with fused primary and secondary; 24 V DC supply
WiringPre-wired and tested at our shop; all field connections on labeled terminal strips; main lugs for incoming power

07Enclosures and panel photos

Panels are built in NEMA 12, 3R, 4 or 4X enclosures to suit the location, including NEMA 4X fiberglass and NEMA 4X stainless steel for food processing and washdown areas. Standard panels handle up to 5 circuits and 15 cable runs; larger panels have been built for up to 36 circuits and 72 runs.

FFCH freezer floor monitor and control data sheet (PDF)